Aerial Bundled Cable (ABC Cable)
Application
Used primarily for overhead and distribution line,or to supply 120/220V aerial service for tem service at construction sites,as a service drop(power pole to service entrance)as a secondary cable(Pole to Pole),or street lighting.For service at 1000V or lower at a maximum conductor temperature of 75℃ or 90℃.
Applicable Standards
ANSI/ICEAS-70-547,ANSI/ICEA S-76-474,NFC 33-209,IEC60502-1,BS7870.50,VDE 027-626 GB/T12527 SANS1418or the standards agreed by both of the customers and us.
- Application
- Construction
- Parameter
- Message
Application
Used primarily for overhead and distribution line,or to supply 120/220V aerial service for tem service at construction sites,as a service drop(power pole to service entrance)as a secondary cable(Pole to Pole),or street lighting.For service at 1000V or lower at a maximum conductor temperature of 75℃ or 90℃.
Applicable Standards
ANSI/ICEAS-70-547,ANSI/ICEA S-76-474,NFC 33-209,IEC60502-1,BS7870.50,VDE 027-626 GB/T12527 SANS1418or the standards agreed by both of the customers and us.
Production Scope:
Voltage:1KV and below.
Phase Core: 1 to 6 Cores,Cross section from 6AWG to 500MCM.
Bare Neutral: Cross Section from 6AWG to 500MCM.
Construction
- Phase Core:
- Conductor: Hard bare copper/Aluminum/Aluminum alloy etc.
- Insulation: PVC/XLPE/PE
- Neutral Conductor(optional): ACSR /AAAC/AAC
- Insulation: PVC/XLPE/PE
- Street Lighting core(optional):
- Conductor: AAC
- Insulation: PVC/XLPE/PE
- *We can design and produce according to client's requirement.
Technical Characteristics
- ABC/NFC33-209
- ABC/ICEA S-76-474
|
Number of Cores x Nominal Cross Section,No.x mm² |
Nominal Thickness of Insulation mm |
Approx Overall Diameter mm |
Approx.mass Kg/Km |
Maximum Conductor Resistance Ω/Km |
Minimum Breaking Load,KN |
Current Rating A |
||
|
Phase core |
Neutral core |
Lighting core |
||||||
|
2×16 |
1.2 |
1.2 |
- |
15 |
130 |
1.91 |
2.3 |
93 |
|
2×16+2×1.5 |
1.2 |
1.2 |
- |
16 |
175 |
1.91/12.1 |
||
|
4×16 |
1.2 |
1.2 |
- |
18 |
260 |
1.91 |
83 |
|
|
4×16+2×1.5 |
1.2 |
1.2 |
|
20 |
310 |
1.91/12.1 |
||
|
2×25 |
1.4 |
1.4 |
- |
18 |
202 |
1.2 |
3.8 |
122 |
|
2×25+2×1.5 |
1.4 |
1.4 |
- |
19.5 |
250 |
1.2/12.1 |
||
|
4×25 |
1.4 |
1.4 |
- |
22 |
404 |
1.2 |
111 |
|
|
4×25+2×1.5 |
1.4 |
1.4 |
- |
24 |
452 |
1.2/12.1 |
||
|
3×35+1×54.6+K×16 (K can be 0,1,2,3) |
1.6 |
1.6 |
1.2 |
28.5/29.5/31/33 |
620/685/750/815 |
0.868/0.63/1.91 |
16.6 |
138/83 |
|
3×50+1×54.6+K×16 (K can be 0,1,2,3) |
1.6 |
1.6 |
1.2 |
30.5/32.5/34/36 |
740/805/870/935 |
0.641/0.63/1.91 |
165/83 |
|
|
3×70+1×54.6+K×16 (K can be 0,1,2,3) |
1.8 |
1.6 |
1.2 |
34.5/36/39/41 |
975/1040/1105/1170 |
0.868/0.63/1.91 |
213/83 |
|
|
3×95+1×70+K×16 (K can be 0,1,2,3) |
1.8 |
1.5 |
1.2 |
37/39.5/42/44 |
1210/1275/1340/1405 |
0.32/0.50/1.91 |
20.5 |
258/83 |
|
3×120+1×70+K×16 (K can be 0,1,2,3) |
1.8 |
1.5 |
1.2 |
38.5/40.5/43.5/46 |
1477/1542/1607/1672 |
0.253/0.50/1.91 |
|
|
|
3×120+1×95+K×16 (K can be 0,1,2,3) |
1.8 |
1.6 |
1.2 |
39.5/41.5/44.5/47 |
1535/1600/1665/1730 |
0.253/0.343/1.91 |
27.5 |
|
|
3×150+1×70+K×16 (K can be 0,1,2,3) |
1.7 |
1.5 |
1.2 |
40.5/42/44.5/48 |
1755/1820/1885/1950 |
0.206/0.50/1.91 |
20.5 |
344/83 |
|
3×150+1×95+K×16 (K can be 0,1,2,3) |
1.7 |
1.6 |
1.2 |
43.2/45.3/47/49 |
1832/1897/1961/2026 |
0.206/0.343/1.91 |
27.5 |
|
|
Item# |
Phase Conductor AWG |
Phase Conductor Insulation mil |
Bare Neutral Messenger Size AWG |
Bare Neutral Messenger Breaking Strength Ib |
Weight Per 1000ft- XLPE Ib |
Weight Per 100Oft-PE Ib |
Ampacity- XLPE A |
Ampacity- XLPE A |
|
Voluta |
6 |
45 |
6 |
1190 |
120 |
130 |
85 |
70 |
|
Periwinkle |
4 |
45 |
4 |
1860 |
176 |
172 |
115 |
90 |
|
Conch |
2 |
45 |
2 |
2850 |
267 |
261 |
150 |
120 |
|
Neritina |
1/0 |
60 |
1/0 |
4380 |
426 |
419 |
205 |
160 |
|
Triton |
2/0 |
60 |
2/0 |
5310 |
530 |
519 |
235 |
185 |
|
Cherrystone |
3/0 |
60 |
3/0 |
6620 |
656 |
643 |
250 |
200 |
|
Razor |
4/0 |
60 |
4/0 |
8350 |
814 |
799 |
315 |
245 |
|
Limpet |
336.4 |
80 |
336.4 |
8680 |
1209 |
1167 |
420 |
325 |