AAAC Rabbit Conductor Cable
AAAC RABBIT conductor is a compact, high-performance All Aluminum Alloy Conductor manufactured using 6201-T81 aluminum alloy, in compliance with ASTM B399, IEC 61089, and BS EN 50182 standards. Named "Rabbit" for its 50 mm² nominal area with 7-strand configuration, it offers superior conductivity (61% IACS) and tensile strength (295 MPa min) compared to ACSR.
- Application
- Construction
- Parameter
- Message
Application
AAAC:Used as bare overhead conductor for primary and secondary distribution.Designed utilizing a high strength aluminum alloy to achieve a high strength-to-weight ratio;affords better sag characteristic.
Aluminum alloy gives AAAC higher resistance to corrosion than ACSR.
Applicable Standards
AAAC:ASTM B-399,BS EN-50182,AS/NZS 1531,DIN 48201,CSA 61089,IEC61089,GB/T 1179,BS3242, NFC 34-125 or the standards agreed by both of the customers and us.
Production Scope
Max.Cross-Section 5000MCM/2500mm²,Max.Stranded number 127Nos.
Construction
- For AAAC: Aluminum alloy wires,concentrically stranded.
- *We can design and produce according to client's requirement.
Technical Characteristics
- AAAC/NFC34-125
- ASTMB399
- BS EN 50182-BS3242
- DIN 48201
- IEC6089-1997
|
Code Name |
Actual section |
Stranding and Wire Diamete |
Overall Diameter |
Mass per unit length |
Rated strength,Min |
Maximum D.C. Resistance at 20℃ |
|
mm² |
No/mm |
mm |
kg/km |
KN |
Ω/km |
|
|
ASTER 22 |
21.99 |
7/2.0 |
6 |
60.2 |
7.15 |
1,498 |
|
ASTER 34.4 |
34.36 |
7/2.5 |
7.5 |
93.5 |
11.17 |
0.959 |
|
ASTER 54.6 |
54.55 |
7/3.15 |
9.45 |
148.9 |
17.73 |
0.604 |
|
ASTER 75.5 |
75.54 |
19/2.25 |
11.3 |
207.4 |
24.55 |
0.438 |
|
ASTER 117 |
116.98 |
19/2.80 |
14 |
321.2 |
38.02 |
0.283 |
|
ASTER 148 |
148.01 |
19/3.15 |
15.8 |
406.6 |
48.12 |
0.223 |
|
ASTER 181.6 |
181.62 |
37/2.50 |
17.5 |
500.3 |
59.03 |
0.183 |
|
ASTER 228 |
227.83 |
37/2.80 |
19.6 |
627.6 |
74.04 |
0.146 |
|
ASTER 288 |
288.34 |
37/3.15 |
22.1 |
794.3 |
93.71 |
0.115 |
|
ASTER 366 |
366.22 |
37/3.55 |
24.9 |
1.008.9 |
115.36 |
0.09 |
|
ASTER 570 |
570.22 |
61/3.45 |
31.1 |
1.576.0 |
185.33 |
0.058 |
|
ASTER 851 |
850.66 |
91/3.45 |
38 |
2.360.7 |
276.47 |
0.039 |
|
ASTER 1144 |
1143.5 |
91/4.0 |
44 |
3.173.4 |
360.22 |
0.029 |
|
ASTER 1600 |
1595.9 |
127/4.0 |
52 |
4.427.5 |
502.72 |
0.021 |
|
Code Name |
Conductor size |
Stranding and Wire Diamete |
Section area |
Overall Diameter |
Mass per unit length |
Rated strength Min |
Maximum D.C. Resistance at 20℃ |
|
|
Nominal |
Actual |
No./mm |
mm² |
mm |
Kg/km |
KN |
Ω/km |
|
|
AWG(MCM) |
mm2 |
|||||||
|
Akron |
30.58 |
15.5 |
7/1.68 |
15.51 |
5.04 |
42.7 |
4.92 |
2.15980 |
|
Alton |
48.69 |
24.7 |
712.12 |
24.67 |
6.35 |
67.56 |
7.84 |
1.58600 |
|
Ames |
77.47 |
39.3 |
712.67 |
39.26 |
8.02 |
107.50 |
12.5 |
0.85470 |
|
Azusa |
123.3 |
62.5 |
7/3.37 |
62.46 |
10.11 |
171.00 |
19.0 |
0.53650 |
|
Anaheim |
155.4 |
78.7 |
7/3.78 |
78.75 |
11.35 |
215.16 |
24.0 |
0.42640 |
|
Amherst |
195.7 |
99.2 |
7/4.25 |
99.20 |
12.75 |
271.50 |
30.2 |
0.33730 |
|
Alliance |
246.9 |
125.1 |
714.77 |
125.10 |
14.30 |
342.60 |
38.1 |
0.26780 |
|
Butte |
312.8 |
158.6 |
19/3.26 |
158.50 |
16.31 |
434.00 |
46.7 |
0.21120 |
|
Canton |
394.5 |
199.9 |
19/3.66 |
199.00 |
18.31 |
547.40 |
59.0 |
0.16760 |
|
Cairo |
456.4 |
236.4 |
19/3.98 |
235.80 |
19.89 |
645.70 |
69.6 |
0.14310 |
|
Darien |
559.5 |
283.5 |
19/4.36 |
283.50 |
21.79 |
776.30 |
83.6 |
0.11810 |
|
Elgin |
652.4 |
330.6 |
19/4.71 |
330.60 |
23.55 |
970.60 |
97.5 |
0.10120 |
|
Flint |
740.8 |
375.4 |
37/3.59 |
375.40 |
25.15 |
1028.00 |
108 |
0.08944 |
|
Greeley |
927.2 |
469.8 |
37/4.02 |
469.80 |
28.14 |
1287.00 |
136 |
0.07133 |
| Code Word | Conductor size | Stranding and Wire Diamete | Sectional Area | Approx. overall Diameter | Approx. mass per unit length | Rated Strength | D.C. Resistance at 20°C |
| mm2 | No. /mm | mm2 | mm | kg/km | kN | Ω/km | |
| Box | 15 | 7/1.85 | 18.8 | 5.55 | 51 | 5.55 | 1.7480 |
| Acacia | 20 | 7/2.08 | 23.8 | 6.24 | 65 | 7.02 | 1.3828 |
| Almond | 25 | 7/2.34 | 30.1 | 7.02 | 82 | 8.88 | 1.0926 |
| Cedar | 30 | 7/2.54 | 35.5 | 7.62 | 97 | 10.46 | 0.9273 |
| Deodar | 35 | 7/2. 77 | 42.2 | 8.31 | 115 | 12.44 | 0.7797 |
| Fir | 40 | 7/2.95 | 47.8 | 8.85 | 131 | 14.11 | 0.6875 |
| Hazel | 50 | 7/3.30 | 59.9 | 9.90 | 164 | 17.66 | 0.5494 |
| Pine | 60 | 7/3.61 | 71.7 | 10.83 | 196 | 21.14 | 0.4591 |
| Holly | 70 | 7/3.91 | 84.1 | 11.73 | 230 | 24.79 | 0.3913 |
| Willow | 75 | 7/4. 04 | 89.7 | 12.12 | 245 | 26.47 | 0.3665 |
| Oak | 100 | 7/4.65 | 118.9 | 13.95 | 325 | 35.07 | 0.2767 |
| Mulberry | 125 | 19/3.18 | 150. 90 | 15.90 | 415 | 44.52 | 0.2192 |
| Ash | 150 | 19/3.48 | 180.7 | 17.40 | 497 | 53.31 | 0.1830 |
| Elm | 175 | 19/3.76 | 211.0 | 18.80 | 580 | 62.24 | 0.1568 |
| Poplar | 200 | 37/2.87 | 239.4 | 20.09 | 659 | 70.61 | 0.1387 |
| Sycamore | 250 | 37/3.22 | 303.2 | 22.54 | 835 | 89.40 | 0.1095 |
| Upas | 300 | 37/3.53 | 362.1 | 24.71 | 997 | 106.82 | 0.0916 |
| Yew | 400 | 37/4.06 | 479.0 | 28.42 | 1319 | 141.31 | 0.0693 |
| Totara | 425 | 37/4.14 | 498.1 | 28.98 | 1372 | 146.93 | 0.0666 |
| Rubus | 500 | 61/3.50 | 586.9 | 31.50 | 1620 | 173.13 | 0.0567 |
| Sorbus | 550 | 61/3.71 | 659.0 | 33.40 | 1823 | 194.53 | 0.0505 |
| Araucaria | 700 | 61/4.14 | 821.1 | 37.26 | 2266 | 242.24 | 0.0406 |
| Redwood | 800 | 61/4.56 | 996.2 | 41.00 | 27532 | 293.88 | 0.0334 |
| Conductor size | Alloy area | Stranding and Wire Diamete | Approx. overall Diameter | Approx. mass per unit length | Rated tensile strength | Maximum resistance D.C. at 20℃ |
| mm2 | mm2 | No/mm | mm | kg/km | daN | Ω/km |
| 16 | 15.89 | 7/1.70 | 5.10 | 43 | 444 | 2.0910 |
| 25 | 24.25 | 7/2.10 | 6.30 | 66 | 677 | 1.3703 |
| 35 | 34.36 | 7/2.50 | 7.50 | 94 | 960 | 0.9669 |
| 50 | 49.48 | 7/3.00 | 9.00 | 135 | 1382 | 0.6714 |
| 50 | 48.35 | 19/1.80 | 9.00 | 133 | 1350 | 0.6905 |
| 70 | 65.81 | 19/2.10 | 10.50 | 181 | 1838 | 0.5073 |
| 95 | 93.27 | 19/2.50 | 12.50 | 256 | 2605 | 0.3579 |
| 120 | 116.99 | 19/2.80 | 14.00 | 322 | 3268 | 0.2854 |
| 150 | 147.11 | 37/2.25 | 15.80 | 406 | 4109 | 0.2274 |
| 185 | 181.62 | 37/2.50 | 17.50 | 500 | 5073 | 0.1842 |
| 240 | 242.54 | 61/2.25 | 20.30 | 670 | 6774 | 0.1383 |
| 300 | 299.43 | 61/2.50 | 22.50 | 827 | 8363 | 0.1120 |
| 400 | 400.14 | 61/2.89 | 26.00 | 1104 | 11176 | 0.0838 |
| 500 | 499.63 | 61/3.23 | 29.10 | 1379 | 13960 | 0.0671 |
| 625 | 626.2 | 91/2.96 | 32.60 | 1732 | 17490 | 0.0540 |
| 800 | 802.09 | 91/3.35 | 36.90 | 2218 | 22402 | 0.0418 |
| 1000 | 999.71 | 91/3.74 | 41.10 | 2767 | 27922 | 0.0335 |
| Code Number | Area | Stranding and wire Diameter | Approx. overall Diameter | Approx. mass per unit length | Rated strenght | D.C. resistance |
| mm2 | mm | Kg/km | kN | Ω/km | ||
| 16 | 18.4 | 7 | 5.49 | 50.4 | 5.43 | 1.7896 |
| 25 | 28.8 | 7 | 6.87 | 78.7 | 8.49 | 1.1453 |
| 40 | 46.0 | 7 | 8.67 | 125.9 | 13.58 | 0.7158 |
| 63 | 72.5 | 7 | 10.80 | 198.3 | 21.39 | 0.4545 |
| 100 | 115.0 | 19 | 13.90 | 316.3 | 33.95 | 0.2877 |
| 125 | 144.0 | 19 | 15.50 | 395.4 | 42.44 | 0.2302 |
| 160 | 184.0 | 19 | 17.55 | 506.1 | 54.32 | 0.1798 |
| 200 | 230.0 | 19 | 19.65 | 632.7 | 67.91 | 0.1439 |
| 250 | 288.0 | 19 | 21.95 | 790.8 | 84.68 | 0.1151 |
| 315 | 363.0 | 37 | 24.71 | 998.9 | 106.95 | 0.0916 |
| 400 | 460.0 | 37 | 27.86 | 1268.4 | 135.81 | 0.0721 |
| 450 | 518.0 | 37 | 29.54 | 1426.9 | 152.79 | 0.0641 |
| 500 | 575.0 | 37 | 31.15 | 1585.5 | 169. 76 | 0.0577 |
| 560 | 645.0 | 61 | 33.03 | 1778.4 | 190.14 | 0.0516 |
| 630 | 725.0 | 61 | 35.01 | 2000.7 | 213.90 | 0.0458 |
| 710 | 817.0 | 61 | 37.17 | 2254.8 | 241.07 | 0.0407 |
| 800 | 921.0 | 61 | 39.42 | 2540.6 | 271.62 | 0.0361 |
| 900 | 1036.0 | 91 | 41.91 | 2861.1 | 305.58 | 0.0321 |
| 1000 | 1151.0 | 91 | 44.11 | 3179.0 | 339.53 | 0.0289 |
| 1120 | 1289.0 | 91 | 46.75 | 3560.5 | 380.27 | 0.0258 |
| 1250 | 1439.0 | 91 | 49.39 | 3973.7 | 424.41 | 0.0231 |